C-11 CONTROLLER

C-11 CONTROLLER

some text
some text
some text
some text
some text
some text
some text
some text

SEMPAL C-11 controller is used in heating, hot water supply, air conditioning systems for weather-depending temperature regulation.

C-11 controller can be used as the main control unit of virtually any standard MHU or in remote controlled regulation systems 

Description

- provides temperature control in a dependent or independent heating system (heat supply);

 - regulates the water temperature in the hot water supply system;

 - regulates the temperature of the coolant in the boiler circuit;

- regulates the air temperature in air conditioning systems;

 - controls various types of pumps;

- The controller is used for various single and double circuit typical heating systems, hot water supply and air conditioning;

- up to 8 channels of temperature measurement;

- up to 4 external digital inputs;

- 2 independent channels of proportional control (heat control loop);

- 4 independent key channels for discrete device control (valves, network, circulation, make-up and charging pumps, etc.);

Specifications:

- temperature measuring range 50 ... 1500 С;

- error of temperature measurement - 0.20 С;

- periodicity of temperature measurement - 2 sec;

- accuracy of temperature maintenance in steady state 0.50 С;

- power supply - from the network of direct current 16V ... 36V, power consumption 4 VA;

- temperature sensor of Pt100 TSP type with a 4-wire connection scheme (cable length up to 500 m);

- operating ambient temperature 0 ... 500 С;

- weight of the device is 250 g, the form factor of the housing is DINREEKA, dimensions with connectors and fastening -165х100х70 mm;

- degree of protection IP44;